Outdoor Load Break Switch Type LDFT1(INDIAN DEVELOPMENT)  - Technical Data

Rated Voltage 12 / 24 / 36 kV
Rated Current 630 A
Rated Short-time current 25 kA Tested in CPRI
Rated making current 50 kA
Rated load breaking current 630 A
Rated closed - loop breaking current 630 A
Rated cable- and line-charging breaking current 10 A
Transformer Off-load breaking current 10 A
complying specification As Per IEC 60265 Tested in CPRI
Rated lightning impulse withstand voltage As Per IEC 60694 Tested in CPRI

Note : 

  • Switch can be supplied with Outdoor HRC Fuses and also with making capacity

  • Switch can be supplied with motor operation and also with remote /wireless operation

  • Switch is suitable for Horizontal and Vertical Mounting

[Outdoor Isolator] [Ring Main] [Indoor L.B. Switch] [Outdoor L.B. Switch] [V.C.B.] [Compact Substation][LFSTP2]